Series MS Magnesense® Differential Pressure Transmitter

Series MS Magnesense® Differential Pressure Transmitter

Service
  • Air and non-combustible, compatible gases(natural gas option available).

Applicable standards

Type Magnehelic & Digital Gauges
Model Name Series MS Magnesense
Wetted Materials Consult factory.
Accuracy ±1% for 0.25″ (50 Pa), 0.5″ (100 Pa), 2″ (500 Pa), 5″ (1250 Pa), 10″ (2 kPa), 15″ (3 kPa), 25″ (5 kPa) ±2% for 0.1″ (25 Pa), 1″ (250 Pa) and all bidirectional ranges.
Stability ±1% FS/year.
Temperature Limits 0 to 150°F (-18 to 66°C)
Pressure Limits 1 psi maximum, operation; 10 psi, burst
Power Requirement 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire).
Size 4″ (101.6 mm) diameter dial face.
Output Signal 4 to 20 mA (2-wire); 0 to 5 V, 0 to 10 V (3-wire).
Zero & Span Adjustments Digital push button
Response Time Field adjustable 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds
Loop Resistance Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 kΩ.
Current Consumption 40 mA max.
Display(optional) 4 digit LCD.
Electrical Connection 4-20 mA, 2-wire: European Style Terminal Block for 16 to 26 AWG. 0-10 V, 3-wire: European Style Terminal Block 16 to 22 AWG.
Electrical Entry 1/2″ NPS Thread. Accessory: Cable Gland for 5 to 10 mm diameter cable
Process Connection 3/16″ (5 mm) ID tubing. Maximum OD 9 mm
Mounting Orientation Diaphragm in vertical position.
Enclosure Rating NEMA 4X (Ip66)